High-Quality SJKM5DC Direct Current Molded Case Circuit Breaker Supplier, Factories

The SJKM5DC(PV) Direct Current Molded Case Circuit Breaker delivers specialized protection for 1500V solar arrays. With 800A breaking capacity and adaptive thermal tripping (derating above 40°C), this DC molded case breaker excels in Category III environments. Its corrosion-resistant housing withstands conductive dust and temperature cycling (-5°C to +50°C), while the arc-control technology minimizes downtime in utility-scale PV systems. The SJKM5DC series is UL-certified for non-explosive environments, offering maintenance-free operation for DC distribution and inverter isolation.

Product Description

Type Designation
SJKM5DC Direct Current Molded Case Circuit Breaker Type Designation
1Manufacturer Code
2Molded Case Circuit Breaker
3Design Serial Number
4PV: Photovoltaic Special | DC: Direct Current Special
5Frame Size Rating
6Number of Poles
7Accessory Code (See Table Below)
8Rated Current
9Operating Voltage
Accessory Code Table
Accessory None Alarm Contact Shunt Release Shunt+Alarm Auxiliary Contact Auxiliary+Alarm Shunt+Auxiliary Shunt+Auxiliary+Alarm Two Auxiliaries Two Auxiliaries+Alarm
Accessory Code 00 08 10 18 20 28 40 48 60 68
Product Display
Technical Parameters
Product Model SJKM5DC
Frame Size Rating 250 315 400 630 800
Rated Current (A) 63A, 80A, 100A, 125A, 140A, 160A, 180A, 200A, 225A, 250A 250A, 315A, 350A, 400A 400A, 500A, 630A 630A, 700A, 800A
Nominal Insulation Voltage (V) 1500V
Rated Impulse Withstand Voltage (KV) 12KV
Type DC PV DC PV DC PV DC PV DC PV
Rated Operating Voltage (V) 2P Shape DC250V, DC500V, DC750V, DC1000V, DC1500V DC250V, DC500V, DC750V, DC1000V, DC1500V
3P Shape DC1000V, DC1250V, DC1500V DC1000V, DC1500V
Rated Ultimate Short-Circuit Breaking Capacity (kA) 2P Shape DC1000V: 15
DC1500V: 5
DC250/500V: 50
DC750/1000V: 25
DC1500V: 7.5
DC1000V: 15
DC1500V: 5
DC250/500V: 50
DC750/1000V: 25
DC1500V: 7.5
DC250/500V: 25
DC750/1000V: 15
DC1500V: 10
DC250/500V: 50
DC750/1000V: 25
DC1500V: 10
DC250/500V: 25
DC750/1000V: 15
DC1500V: 10
DC250/500V: 50
DC750/1000V: 25
DC1500V: 10
DC250/500V: 25
DC750/1000V: 15
DC1500V: 10
DC250/500V: 50
DC750/1000V: 25
DC1500V: 10
3P Shape DC1500V: 20 DC1000/1250/1500V: 25 DC1500V: 20 DC1000/1250/1500V: 25 DC1000V: 30
DC1500V: 25
DC1000V: 40
DC1500V: 30
DC1000V: 30
DC1500V: 25
DC1000V: 40
DC1500V: 30
DC1000V: 30
DC1500V: 25
DC1000V: 40
DC1500V: 30
Rated Short-Circuit Breaking Capacity (kA) 100% Icu
Connection Mode 2P Shape (Figure 1), 3P Shape (Figure 2) 2P Shape (Figure 1), 3P Shape (Figure 3)
Isolation Function YES
Selective Category A
Mechanical Life (Cycles) 20,000 10,000
Electrical Life (Cycles) 1,500 1,000 800 500
Flashover Distance (mm) 2P Shape ≤50 ≤100 ≤50 ≤100
3P Shape 200 × 73 × 135 270 × 130 × 156
Overall Dimensions (mm) 200 × 107 × 135 310 × 182 × 156
Reference Ambient Temperature (℃) -
Internal & External Accessories
Alarm Switch

Function: The Alarm Switch features an intelligent alarm system that automatically triggers a fault signal when tripped by overload, short circuit, or external release, while remaining inactive during normal operations - making it ideal for automation system integration.

Tripping Characteristics:

Alarm Switch Tripping Diagram
Auxiliary Switch

Function: Equipped with dual-contact auxiliary switches (NO+NC), the SJKM1E ECB provides real-time remote status monitoring and interlocking by reversing contact states during opening/closing operations.

Tripping Characteristics:

Auxiliary Switch Diagram
Shunt Release

Function: A shunt release is a device that remotely trips a circuit breaker using electric current; it automatically cuts off the signal circuit after the circuit breaker has tripped.

Tripping Characteristics:

Shunt Release Diagram
Voltage Specification AC50Hz: 24V, 110V, 230V, 400V | DC: 24V, 110V, 220V
Tripping Characteristics When the control voltage is between 70% and 110% of the rated value, the shunt release can trip the circuit breaker.
Outline & Installation Dimensions
Outline and Installation Dimensions
Model Specification Overall Dimensions (mm) Mounting Dimensions (mm)
L W H L1 L2 W1 H1 H2 a b 4-Ød
250/2P2007613510.59.5229826/1614.5
250/3P20010713510.59.5229826351614.5
400/2P2571401701610.530943643.51976.5
400/3P2571841701610.530943643.51976.5
630/2P2571401701610.530943643.51976.5
630/3P2571841701610.530943643.51976.5
* Conductor Cross-Section
Rated Current (A) 63 80 100 125/140 160 180/200/225 250 280/300/315 350/400 500/630 700/800
Wire Cross-Section (mm²) 16 25 35 50 70 90 120 Copper Bar 20×5×2 Copper Bar 40×5 Copper Bar 40×8 Copper Bar 40×5×2
Frequently Asked Questions (FAQ)
What applications are best suited for the SJKM5DC series circuit breaker?
The SJKM5DC series is engineered specifically for direct current (DC) installations, notably large-scale solar photovoltaic (PV) power systems, DC energy storage, and industrial DC power distribution setups requiring up to 1500V DC protection.
What is the highest operational voltage supported by the SJKM5DC?
The SJKM5DC circuit breaker supports operating voltages up to DC 1500V across both 2P and 3P structural configurations, featuring a rated insulation voltage (Ui) of 1500V.
What accessories can be installed with the SJKM5DC?
It accommodates internal and external accessories including Alarm Contacts, Auxiliary Contacts (NO+NC), and Shunt Releases, available as individual units or combined accessory configurations.
What is the breaking capacity performance of this DC MCCB?
The SJKM5DC provides high breaking capability with rated service short-circuit breaking capacity (Ics) certified at 100% of the ultimate short-circuit breaking capacity (Icu), ensuring reliable performance under critical fault conditions.
What are the mechanical and electrical endurance ratings?
Depending on frame rating, the SJKM5DC supports mechanical endurance up to 20,000 operations and electrical endurance ranging between 500 to 1,500 operations.