China SJKM1L Earth Leakage Circuit Breaker ELCB for Industrial Safety Factory, Companies

The SJKM1L Earth Leakage Circuit Breaker ELCB provides comprehensive electrical protection for 400V/50Hz systems (up to 800A). This SJKM1L ELCB combines overload, short-circuit, and 30mA-30A residual current protection to prevent fire hazards from ground faults. Available in M-type (molded case) and H-type (high-breaking capacity) versions, it features 800V insulation and vibration resistance. The breaker's compact design allows for both vertical and horizontal installation in distribution panels. This SJKM1L ELCB is ideal for motor circuits, industrial plants, and power distribution systems requiring infrequent switching and reliable earth leakage protection. 

Product Description

Type Designation

SJKM1L-4 Type Designation Code
① Manufacturer Code
② Molded Case Circuit Breaker (MCCB)
③ Design Serial Number
④ With Residual Current Protection
⑤ Frame Size
⑥ Breaking Capacity: L (Standard), M (Medium), H (High)
⑦ Operation: None (Manual), Z (Rotary Handle), D (Motorized)
⑧ Poles: 3 (3-Pole), 4 (4-Pole)
⑨ Trip Type & Accessory Code (See Table 1)
⑩ Application Code: None (Distribution), 2 (Motor Protection)
⑪ 4-Pole Code (A/B/C/D for Neutral), 3-Pole: No Code
⑫ Alarm Module: Ⅰ (Alarm + Trip), Ⅱ (Alarm Only)
Notes:
Frame Size: 1N25 (125A), 2N50 (250A), 4N00 (400A), 6N30 (630A), 8N00 (800A)

Product Display

SJKM1L Earth Leakage Circuit Breaker Angle View
SJKM1L Earth Leakage Circuit Breaker Front View

Trip - Opening Method and Accessory Code

SJKM1L Trip Opening Method and Accessory Code Chart

Main Parameters and Technical Performances

Model SJKM1LE-125 SJKM1LE-250 SJKM1LE-400 SJKM1LE-630, 800
Maximum Rated Current of Shell Frame Grade A 125 250 400 800
Rated Current In A 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 125, 160, 180, 200, 225, 250 250, 315, 350, 400 400, 500, 630, 700, 800
Number of Poles 3 4 3 4 3 4 3 4
Rated Insulation Voltage Ui V AC800
Rated Working Voltage Ue V AC400
Rated Impulse Withstand Voltage Uimp V 8000
Arc - Quenching Distance mm 50 50 100 100
Breaking Capacity
Icu / Ics
Level L M L M L M L M
AC400V (Icu) 35 / 50 35 / 50 50 / 65 50 / 65
AC400V (Ics) 22 / 35 25 / 35 35 / 42 35 / 42
Rated Residual Short - Circuit Making (Breaking) Capacity Icu/4 8.75 12.5 15.75 16.25
Rated Residual Operating Current I△n (mA) Non - delay type 30/50/100, 100/300/500 30/50/100, 100/300/500 100/300/500 300/500/1000
Delay type 100/300/500 100/300/500 100/300/500 300/500/1000
Rated Residual Non-Operating Current 1/2I△n 1/2I△n 1/2I△n 1/2I△n
Number of Operating Performances Energized 1500 1000 1000 1000
De - energized 8500 7000 4000 4000
Total number of times 10000 8000 5000 5000
Operating Time of Residual Current Protection 2I△n 2I△n 5I△n 10I△n
Maximum Breaking Time (S) Non - delay type 0.2 0.1 0.4 0.04
Delay type 0.5/1.15/2.15 0.35/1/2 0.25/0.9/1.9 0.25/0.9/1.9

Outline and Installation Dimensions

◆ Outline and Installation Dimensions of the Circuit Breaker After Wiring (Rear-Panel Wiring)
Circuit breaker rear-panel wiring dimensions
Circuit breaker rear - panel wiring
Model Overall Dimensions (mm) Installation Dimensions (mm)
a1 b1 ΦD Φd
L1 L2 L3 H1 H2 3P 4P 3P 4P
SJKM1LE-125 162 132 35 53 93 72 102 90 132 22 5.5
SJKM1LE-250 173 144 35 55 100 87 122 93 144 24 5.5
SJKM1LE-400 267 224 37 48.5 108.5 124 172 164 224 26 6.5
SJKM1LE-630/800 295 243 37 62 62 178 248 158 243 48 7.0
◆ Outline and Installation Dimensions of Plug - in Type Rear - panel Wiring
Plug-in type rear-panel wiring dimensions
Model w L A H1 G G1 a b Φd
3P 4P 3P 4P
SJKM1LE-125 91 125 168 38 50 33 28 60 90 56 6.5
SJKM1LE-250 107 145 186 46 50 33 37 70 105 54 6.5
SJKM1LE-400 149 200 280 55 60 38 46 60 108 129 8.5
SJKM1LE-630/800 210 280 305 62 87 60 22 90 162 146 11
◆ Outline and Installation Dimensions of the Circuit Breaker with Front - panel Wiring
Circuit breaker front terminal wiring diagram
Circuit Breaker Front Terminal
Model Pole Overall Dimensions (mm) Installation Dimensions (mm)
L1 L2 L3 L4 a b Φd
SJKM1LE-125 2 65 151 110 75 - 129 2×Φ4.5
3 93 151 110 92 30 129 4×Φ4.5
4 123 151 110 92 60 129 6×Φ4.5
SJKM1LE-250 2 75 165 110 90 - 129 2×Φ4.5
3 107 165 110 90 35 126 4×Φ4.5
4 142 165 110 90 70 126 6×Φ4.5
SJKM1LE-400 3 154 257 146 106 44 194 4×Φ4.5
4 198 257 146 106 94 194 6×Φ4.5
SJKM1LE-630 / 800 3 210 280 155 116 70 243 4×Φ7
4 280 280 155 116 140 243 6×Φ7

Frequently Asked Questions (FAQ)

What does the SJKM1L series MCCB protect against?

The SJKM1L series Molded Case Circuit Breaker provides comprehensive protection against overloads, short-circuits, and residual current (earth leakage), guarding electrical circuits and equipment from fire hazards and electrocution.

What frame sizes and rated currents are available?

The available frame sizes are 125A, 250A, 400A, 630A, and 800A, with rated current options covering a wide range starting from 16A up to 800A across different frame configurations.

What are the available operation and control methods?

The circuit breakers support three operation types: standard manual toggle operation, rotary handle mechanism (Z), and motorized electric mechanism (D).

What is the difference between non-delay and delay type residual current protection?

Non-delay types offer immediate tripping upon residual fault detection (breaking time from 0.04 to 0.4 seconds) for personal safety, while delay types allow a calibrated time delay (up to 2.15 seconds) to achieve selectivity in distribution panels.

What wiring and installation configurations are supported?

The breaker series accommodates front-panel wiring, rear-panel wiring, and plug-in type rear-panel wiring solutions to suit various switchboard and enclosure integration requirements.