OEM SafeRing-40.5 Gas Insulated Ring Main Unit (RMU) -SF6 Sealed Switchgear Supplier, Company

Gas Insulated Ring Main Unit (RMU) is compact high-performance SF6 sealed medium-voltage switchgear built for dependable power distribution. Equipped with SF6 gas insulation, it provides outstanding arc-quenching performance, low maintenance requirements and high safety even in limited spaces. Supporting both ring-main and radial network configurations, this modular RMU allows flexible grid integration and can be installed indoors or outdoors. It effectively blocks external contamination to extend service life and reduce operation risks. Compliant with IEC and IEEE standards, it delivers stable performance under harsh conditions, widely adopted in urban power grids, industrial facilities and renewable energy projects.

Product Description

Type Designation

Safering-40
1 Manufacturer Code
2 Model Type
3 Rated Voltage: 40.5 Rated voltage 40.5KV
4 Cabinet Type: C: Load Switch Cabinet;  F: Fuses Switchgear Cabinet;  V: Vacuum Circuit Breaker Cabinet;  M: Measuring cabinet; SV, SL, Bus Sectionalizing Switchgear;  PT: PT Cabinet (Co-enclosure cabinet composed of any combination of C, F, V, S, VSL.)
5 Rated Current: 2500 Rated Current 2500A; 3150 Rated Current 3150A
6 Expansion Type: I: Left Extension; D: Right Extension; ID: Both Sides; Blank: extendable
7 Cable entry/exit method: L: Left; R: Right; LR: Both; Blank: Front

Product Display

Technical Parameters

Name Unit Parameter
Rated voltage kV 12 40.5
Rated current A 1250-3150 1250-2500
Rated frequency Hz 50
Rated short-time withstand current k/Vs 25,31.5
Rated peak withstand current kA 63,80
Rated short-circuit current duration s 4
Rated short-circuit breaking current kA 25,31.5
Rated short-circuit making current kA 63,80
Duration of arcing S 0.5
Mechanical life Circuit breaker Times 2000 10000
Isolating switch 3000
Earthing switch 3000
Electrical life of circuit breaker Times 30
Rated inflation pressure(20℃ gauge pressure) MPa 0.05
Minimum functional pressure(20℃ gauge pressure) 0.03
Annual leakage rate of SF₆gas ≤0.5%
Rated insulation level Rated power frequency 1min withstand voltage(effective value) Phase to phase kV 42 95
Isolation fracture,vacuum fracture 48 118
Rated lightning impulse withstand voltage(peak value) Phase to phase 75 185
Isolation fracture,vacuum fracture 85 215
Auxiliary control circuit Rated voltage V DC:110,220 AC:110,220
1min power frequency withstand voltage 2000
Cabinet protection grade Cabinet shell IP4X
Inflatable compartment - IP65
Category of loss of operation continuity - LSC2B
Temperature rise test A 1.1lr
Main circuit resistance 1250 μΩ 85 100
2000 65
2500 60 60
3150 50
Partial discharge Test voltage kV 1.1×12/√3 1.1X40.5/√3
Single insulating element pC ≤3
Complete machine ≤50
Service life Year ≥30

Outline and Structure Diagram of Switch Cabinet

SafeRing-40-7
1. Small bus room 11. CM-35 arrester
2. Instrument room 12. Pressure release channel
3. Inflatable compartment of main bus 13. Cable plug
4. Station disconnector 14. Cable socket
5. Operating mechanism room 15. Test socket plug
6. Circuit breaker 16. Test socket
7. Inflatable compartment of circuit breaker 17. Branch bus
8. Cable chamber 18. Pressure relief device
9. Current transformer 19. Main bus
10. Cable 20. Bus coupler socket
21. Bus coupler
Note:
a (cabinet width): 600mm, 800mm;
b (cabinet depth): 12kV depth is 1420; The depth of 40.5kV is 1620.
SafeRing-40-8

Ordering Notice

Product operating site and special requirements:

  1. Provide product ordering drawings, which should include wiring diagrams and indicate transformer capacity, main component model specifications, distribution branch circuits, and capacity.
  2. When it is necessary to configure electric energy metering and reactive power automatic compensation devices, the requirements for the configuration of the metering meter and transformer should be provided, and the capacity of the compensation capacitor should be indicated.
  3. Specify the requirements for surface treatment of the product.

Frequently Asked Questions (FAQ)

What are the available rated voltage levels for this switchgear?

This product series is available in both 12 kV and 40.5 kV rated voltage options.

What is the ingress protection (IP) rating of the switchgear?

The cabinet enclosure provides an IP4X protection grade, while the gas-inflatable compartment meets an IP65 protection level.

What is the expected service life and annual gas leakage rate?

The switchgear is engineered with an expected operational service life of at least 30 years, and an annual SF₆ gas leakage rate maintained at or below 0.5%.

What cabinet unit configurations can be combined?

The system supports modular combinations including Load Switch Cabinets (C), Fuse Switchgear Cabinets (F), Vacuum Circuit Breaker Cabinets (V), Measuring Cabinets (M), Bus Sectionalizing Switchgear (SV, SL), and PT Cabinets.

What dimensions are typical for the 12kV vs 40.5kV cabinets?

Cabinet widths are typically 600mm or 800mm. The standard depth is 1420mm for the 12kV configuration and 1620mm for the 40.5kV configuration.

What critical information must be provided when placing an order?

Orders require wiring drawings indicating transformer capacity, component specifications, distribution branch circuits, energy metering/compensation requirements, and surface finish instructions.

Related Products