Wholesale SafeRing-12 Fully insulated inflatable ring switchgear with Insulation Protection Manufacturers, Companies

MR-SafeRing-12/24 Fully Insulated Inflatable Ring Switchgear is a SF6 gas-sealed solution for 10-24kV grids. This fully insulated inflatable ring switchgear features stainless-steel modules with 30-year lifespan, immune to harsh environments. Its coaxial load switch prevents misoperation while enabling flexible expansion. Certified by China's High Voltage Test Center, it supports vacuum breakers for substations, airports and metros. With 0.15-0.4bar pressure monitoring and automation readiness, this maintenance-free fully insulated inflatable ring switchgear ensures reliable power distribution.

Product Description

Type Designation
SafeRing-12 Fully insulated inflatable ring switchgear designation structure
1 Manufacturer Code
2 Model Type
3 Rated Voltage: 12 (12 kV); 24 (24 kV)
4 Cabinet Type: C: Load Switch Cabinet; F: Fuses Switchgear Cabinet; V: Vacuum Circuit Breaker Cabinet; M: Measuring Cabinet; SV, SL: Bus Sectionalizing Switchgear; PT: PT Cabinet (Co-enclosure cabinet composed of any combination of C, F, V, S, SL)
5 Rated Current: 630 (630 A); 1250 (1250 A)
6 Expansion Type: I: Left Extension; D: Right Extension; ID: Both Sides; Blank: extendable
7 Cable Entry/Exit Method: L: Left; R: Right; LR: Both; Blank: Front
Performance Indicators
Unit Code Description Unit Code Description
C Standard Single-Bushing Load Switch Unit - Top Busbar Bushing
F Load Switch-Fuse Combination Unit SL Bus Coupler Unit
V Circuit Breaker Unit M Metering Unit
D Cable Incoming Unit (Non-Switch) PT PT Unit
+ Busbar Side Bushing 1K2(4) Load Switch Unit with Double Bushings
Technical Item Specification Normal Operating Environmental Conditions
SF6 Gas Pressure Absolute Pressure at 20℃: 1.4 BAR Maximum Temperature 40℃
Annual Gas Leakage Rate ≤0.2% per year Minimum Temperature -40℃
Protection Level IP67 Maximum Average Relative Humidity ≤95%
Gas Chamber Stainless Steel Thickness 3.0 mm Altitude ≤2000 meters
Busbars Color Coding
Switchgear Busbar 400 mm² Cu Switchgear Front Panel RAL7012
Switchgear Grounding 150 mm² Cu Side Panels & Cable Room Front Cover RAL7035
Compliant Standards
GB/T11022 GB3906 GB1985 GB3309 IEC60129 IEC60298 -
GB16926 GB38041 GB1984 IEC60056 IEC60265 IEC60420 IEC60694
Product Display
Technical Parameters
Model C Module F Module V Module CB Module
Composite Switch Combined Electrical Apparatus Vacuum Switch Disconnecting/Earthing Switch Vacuum Circuit Breaker Disconnecting/Earthing Switch
Rated Voltage kV 12 12 12 12 12 12
Rated Frequency Hz 50 50 50 50 50 50
Power Frequency Withstand Voltage (Phase-to-Phase/Port) kV 42/48 42/48 42/48 42/48 42/48 42/48
Lightning Impulse Withstand Voltage kV 75/85 75/85 75/85 75/85 75/85 75/85
Rated Current A 630 Note 1 630 - 1250/630 -
Rated Closed-loop Breaking Current A 630 - - - - -
Rated Cable Charging Breaking Current A 135/135 - - - - -
Rated Short-circuit Making Current (Peak) A 50 80 - - - -
Rated Peak Withstand Current kA 50 - - - - -
Rated Short-time Withstand Current kA/3s 20 - - - - -
Rated Short-circuit Breaking Current kA - 31.5 20 - 25 -
Rated Transfer Current A - 1750 - - - -
Maximum Current of Associated Fuse A - 125 - - - -
Loop Resistance μΩ ≤300 ≤600 - - - -
Mechanical Life Operations 5000 3000 5000 2000 5000 5000
Note: 1) Depends on the current rating of the fuse.
MR-SafeRing-12 Gas-insulated Switchgear Structure
Safering-12 Gas-insulated Switchgear Structural View
1. Fuse Compartment 5. Serial Number Label 9. Cable Compartment 13. Load Switch Operation Port
2. Capacitive Voltage Indicator 6. Schematic Diagram 10. RTU Mounting Compartment 14. Earthing Switch Operation Port
3. Short-circuit Ground Fault Indicator (Accessory) 7. Fuse Blow Indicator 11. Key Lock (Accessory) 15. Disconnector Operation Port
4. Pressure Indicator 8. Panel-mounted Padlock Device 12. Circuit Breaker Operation Port 16. Trip Button
17. Close Button
Safering-12 Switchgear Sectional Drawing
Frequently Asked Questions (FAQ)
What are the main applications of the SafeRing-12 switchgear?
SafeRing-12 is designed for 12kV and 24kV medium-voltage secondary distribution networks, compact substations, light industrial systems, and commercial installations needing reliable power distribution.
What level of ingress protection (IP) does the gas chamber offer?
The stainless steel gas chamber provides an IP67 protection rating, ensuring all high-voltage live parts are completely sealed against dust, water immersion, and harsh external environments.
Can the SafeRing-12 switchgear be expanded on site?
Yes, multiple expansion options are supported, including left extension (I), right extension (D), and dual-side extensions (ID) through external busbar connectors without handling SF6 gas on site.
What is the gas leakage rate and maintenance requirement?
With an annual leakage rate of ≤0.2% per year and sealed pressure system technology, the switchgear operates virtually maintenance-free throughout its service life.
Which international standards are met by this equipment?
The system conforms strictly to key international standards including IEC 60298, IEC 60265, IEC 60129, IEC 60694, and IEC 60056, alongside national GB standards.