ODM XGN15-24 Medium Voltage Switchgear Sf6 Insulated Ring Main Unit Manufacturers, Companies

XGN15-24 AC Metal Enclosed Ring Network Switchgear is a reliable 24kV/50Hz distribution solution with robust metal-clad construction. This AC metal enclosed ring network switchgear supports FLN36/48-12 SF6 load switches and ABB/Schneider vacuum breakers (VS1/VD4). Featuring manual/electric operation and FTU compatibility, it enables smart grid automation. The modular AC metal enclosed ring network switchgear design allows flexible deployment in urban grids, industrial parks, and critical sites like airports. With mechanical interlocking and compact dimensions, this air-insulated switchgear ensures safe, maintenance-free operation for cable networks and renewable energy systems.

Product Description

Type Designation
XGN15-24 Medium Voltage Switchgear Type Designation
Item Description
1Box-type Construction
2Fixed Type
3Indoor Type
4Design Serial Number
5Rated Voltage kV
6Rated Current A
7I: FLN36-12 Load Switch; Ⅱ: FLN48-12 Load Switch
Technical Parameters
No. Parameter Unit Value
1Rated VoltagekV12
2Rated FrequencyHz50
3Main Busbar Rated Current / Maximum Fuse RatingA630, 125
4Main Circuit & Earth Circuit Rated Short-time Withstand CurrentkA/S203
5Main Circuit & Earth Circuit Rated Peak Withstand CurrentkA50
6Main Circuit & Earth Circuit Rated Short-circuit Making CurrentkA50
7Load Switch Full-capacity Breaking Operationsoperations100
8Fuse Breaking CapacitykA31.5, 40
9Rated Closed-loop Breaking CurrentA630
10Rated Transfer CurrentA1600
11Mechanical Enduranceoperations2000
121-minute Power Frequency Withstand Voltage (phase-to-phase / earth / isolation)kV42, 48
13Lightning Impulse Withstand Voltage (phase-to-phase / earth / isolation)kV75, 85
14Secondary Circuit 1-minute Power Frequency Withstand VoltagekV2
15Protection Class-IP3X
Product Display
Environmental Conditions
Altitude: Not exceeding 2000m.
Ambient Temperature: Operating range from -25°C up to +40℃.
Ambient Humidity: Daily average ≤ 95%; Monthly average ≤ 90%.
Seismic Capacity: Grade 8 protection capability.
Operational Atmosphere: Free of explosive and corrosive gases; installation site without violent vibration or severe impact.
Schematic Diagram
XGN15-24 Schematic Diagram Layout
1. Operating Mechanism 4. Instrument Compartment 7. Fuse
2. Load Switch 5. SF6 Voltage Meter 8. Lower Grounding Switch
3. Cabinet Body 6. High-voltage Live Display
Auxiliary Equipment
XGN15-24 Auxiliary Equipment Diagram
Fault Indicator The DJD-1 short-circuit grounding fault indicator uses logic circuits for over-current alerts and manual reset, equipped with sensors on cables and a display unit for quick fault detection.
Condensation Controller Monitors ambient temperature and humidity in real-time, automatically activating integrated heaters at 85% RH to eliminate moisture buildup (rated power: 75-100W).
FTU & Communication Module The DAT-1L distribution automation terminal provides complete SCADA integration with 48 remote signaling channels, automated self-diagnosis, and protocol support for IEC101, MODBUS, and more.
Current Limiting Fuse Engineered specifically for 24kV/50Hz indoor switchgear systems (292mm length) to deliver rapid interruption against high overcurrent and short-circuit faults.
Frequently Asked Questions
What is the standard rated voltage and operational frequency?
The system operates at a standard rated operational voltage of 12kV with an alternating current frequency of 50Hz.
Which load switches are compatible with this switchgear series?
The switchgear is engineered to accommodate either FLN36-12 (Option I) or FLN48-12 (Option II) medium-voltage load break switches.
What is the ingress protection and mechanical endurance level?
The cabinet enclosure provides an IP3X protection rating and offers high mechanical durability rated for up to 2,000 standard switching cycles.
What are the maximum ambient environmental limitations?
It is rated for altitudes up to 2000m, operating temperatures from -25°C to +40°C, and seismic conditions up to Grade 8, free from corrosive gases.
How does the unit prevent internal moisture and track faults?
It features an integrated condensation controller running heating elements at 85% RH, alongside the DAT-1L FTU and DJD-1 fault indicators for real-time monitoring and automation.