High-Quality SC(B)13 Type 10kV Series Resin Insulation Dry Type Power Transformer Factories, Factory

The SC(B)13 series 10kV resin insulation dry type power transformer is engineered for exceptional reliability and extended service life in critical applications. Constructed with high-grade epoxy resin and advanced manufacturing processes, it delivers superior fireproof, pollution-free, and moisture-resistant performance. Ideal for high-rise buildings, commercial complexes, and industrial plants, this transformer ensures stable power distribution with low energy loss and minimal maintenance requirements. Its robust design withstands harsh environments, making it a cost-effective solution for modern power systems.

Product Description

Type & Meaning

SC(B)13-3 Transformer Designation
Code Index Designation Meaning
1 Three-Phase Transformer
2 Resin Cast Type
3 Foil-Wound Coil
4 Performance Level Code
5 Rated Capacity (kVA)
6 Voltage Class (kV)

Applicable Standards

  • GB6450-1986: Dry-Type Power Transformers
  • GB/T10228-2008: Technical Parameters and Requirements for Dry-Type Power Transformers
  • GB/T17211-1998: Loading Guide for Dry-Type Power Transformers
  • GB1094.3-2003: Power Transformers - Part 3: Insulation Levels, Dielectric Tests and Air Clearances
  • JB/T10088-2004: Sound Levels for 6~500kV Power Transformers
  • JB/T56009-1998: Product Quality Grading for Dry-Type Power Transformers

Product Display

SC(B)13 Dry Type Power Transformer View
SC(B)13 Dry Type Power Transformer Right View

Technical Parameters

Technical Parameters of SC(B)13 Series 10kV Epoxy Resin Cast Dry-Type Power Transformers

Rated Capacity (kVA) Voltage Combination & Tap Range Connection Symbol No-Load Loss (W) Load Loss (W) 120° No-Load Current (%) Short-Circuit Impedance (%) Main Unit Weight (kg) Overall Dimensions (mm) Wheelbase (mm)
High Voltage (kV) Tap Changer (%) Low Voltage (kV) Length×Width×Height (Without Enclosure) Length×Width×Height (With Enclosure)
30 6
6.3
6.6
10
10.5
11
±5
Or
±2×2.5
0.4 Yyn0
Or
Dyn11
130 710 2.4 4 380 820×600×820 - 550×550
50 210 1000 2.1 480 850×600×850 - 550×550
80 280 1380 1.8 600 950×600×950 - 550×550
100 300 1570 1.8 750 1040×600×1000 1300×1000×1300 550×550
125 340 1850 1.6 850 1080×600×1050 1300×1000×1300 550×550
160 390 2130 1.6 950 1120×770×1100 1400×1000×1400 710×660
200 440 2530 1.4 1150 1160×770×1150 1450×1100×1450 710×660
250 520 2760 1.4 1350 1220×770×1200 1500×1150×1500 710×710
315 640 3470 1.2 1600 1260×770×1250 1550×1150×1550 710×710
400 710 3990 1.2 1750 1320×770×1300 1600×1150×1600 710×710
500 800 4880 1.2 2050 1360×820×1350 1650×1200×1650 760×710
630 900 5960 1.0 6 2400 1450×820×1410 1800×1250×1800 760×710
800 1060 6960 1.0 2700 1480×980×1550 1800×1250×1800 920×820
1000 1240 8130 1.0 3200 1520×980×1600 1850×1250×1850 920×820
1250 1460 9690 1.0 3700 1600×980×1650 1900×1250×1900 920×820
1600 1710 11730 1.0 4500 1680×980×1700 1950×1300×1950 920×920
2000 2170 14450 0.8 4800 1760×980×1800 2000×1300×2100 920×920
2500 2560 17170 0.8 5300 1900×980×1900 2200×1400×2200 1020×920

Notes:

1. For the on-load tap-changing SCZ(B)13 series transformers, only the following data are adjusted: the weight increases by 100kg, the side a (where the on-load tap-changer is installed) increases by 650mm, and the front b increases by 750mm.

2. The high-voltage side of the on-load tap-changing transformer can provide a voltage regulation range of ±4×2.5%.

3. The weight and overall dimension data in the table are for reference only; no prior notice will be given for any changes.

Product Features

  • Safety & Eco-friendly: Safe, fireproof, and pollution-free; can operate directly at the load center.
  • High Reliability: High mechanical strength, strong short-circuit withstand capability, low partial discharge, good thermal stability, and long service life.
  • Energy Efficiency: Low loss, reduced noise level, distinct energy-saving performance, and maintenance-free operation.
  • Superior Thermal Performance: Efficient heat dissipation and high overload capacity; capacity can be significantly increased with forced air cooling.
  • Moisture Resistance: Excellent moisture resistance, making it suitable for high humidity and harsh environment applications.
  • Intelligent Monitoring: Can be configured with an advanced temperature protection system that auto-monitors and displays phase temperatures, triggers cooling fans, and executes alarm/trip functions.
  • Compact & Cost-Effective: Compact dimensions, light total weight, minimal floor area required, and lowered overall installation expense.

Frequently Asked Questions

Q What does the SC(B)13 model designation represent?
In the model code SC(B)13, "S" indicates a three-phase transformer, "C" denotes epoxy resin casting, "B" specifies a foil-wound low voltage coil, and "13" refers to the specific performance and energy efficiency level standard.
Q What rated capacities are available in the SC(B)13 transformer series?
The series provides standard rated capacities starting from 30 kVA up to 2500 kVA, accommodating a broad spectrum of commercial, industrial, and utility power distribution demands.
Q Can these transformers be deployed in high-humidity or harsh environments?
Yes. The epoxy resin cast coil provides superior moisture and pollution resistance, allowing the transformer to perform reliably in humid, contaminated, or demanding conditions without risk of insulation deterioration.
Q How does the intelligent temperature control system work?
The system automatically tracks and displays individual winding temperatures in real time on a single interface. It manages automatic fan start/stop for optimal thermal regulation and provides integrated alarm and trip mechanisms to protect against overheating.
Q What changes occur when choosing the on-load tap-changing (SCZ(B)13) version?
Selecting the on-load tap-changing variant increases the total unit weight by approximately 100 kg, expands the tap-changer installation side (side a) by 650 mm, and widens the front (side b) by 750 mm, while offering a regulation range of ±4×2.5%.
Q What national and industry standards do these dry-type transformers comply with?
They comply with recognized industry and national criteria, including GB6450, GB/T10228, GB/T17211, GB1094.3, JB/T10088, and JB/T56009 standards for dry-type power transformers.