OEM Intelligent wireless automatic gas fire extinguishing device-Hot Aerosol Series Manufacturer, Factory

Our automatic gas fire extinguishing devices provide comprehensive protection against electrical fires. These intelligent devices monitor wire temperature, ambient temperature, and smoke in real-time. Featuring multiple communication options (RS485, 4G, Lora), these automatic gas fire extinguishing devices enable wireless data upload to cloud platforms for remote monitoring and control via computer or mobile app. With a modular design for easy cartridge replacement, our automatic gas fire extinguishing devices, including the QRR and YF Hot Aerosol series, offer reliable, cost-effective solutions for various protected spaces.

Product Description

Type Designation

QRR MR
Model Communication Method Key Features Ideal For
QRR□G/S-MR1 Standalone All-in-one unit with integrated detection & extinguishing. No external communication. Basic protection for small, self-contained spaces.
QRR□G/S-MR2 RS485 Wired Can be integrated into a central fire alarm control panel for centralized monitoring. Buildings or facilities requiring a centralized wired monitoring system.
QRR□G/S-MR3 LORA Wireless Long-range wireless communication. Flexible installation with low network setup cost. Areas with distributed layouts or where wiring is difficult.
QRR□G/S-MR4 4G Wireless Connects directly to the cloud platform. Supports remote monitoring and control via mobile app. Multi-site or cross-regional facilities requiring remote, centralized management.

Product Display

MR QRR0
MR QRR0

Product Features

√

Simultaneous online detection of wire temperature, ambient temperature, and smoke to prevent electrical fire hazards.

√

Equipped with various communication interfaces such as RS485, 4G, and Lora.

√

Wireless data upload to the cloud platform enables viewing of on-site data and remote control via computer or mobile app from any location.

√

Functions include real-time data collection, historical curves, event recording, and trend analysis.

√

Two-segment modular product design allows easy replacement of the extinguishing cartridge after use, enabling repeated use and reducing operational costs.

Technical Parameters

Function configuration QRR □ G/S-MR1 QRR □ G/S-MR2 QRR □ G/S-MR3 QRR □ G/S-MR4
Communication Method / RS485 LORA/433MHz 4G
Dimensions 0.1G/S: 66*45*90mm
0.3G/S: 66*45*255mm
0.1G/S: 66*45*170mm
0.3G/S: 66*45*335mm
0.1G/S: 66*45*170mm
0.3G/S: 66*45*335mm
0.1G/S: 66*45*170mm
0.3G/S: 66*45*335mm
Operating Voltage / DC24V
Quantity 0.1G/S: 100g±2g
0.3G/S: 300g±2g
Protected Space 0.1G/S: ≤1m³
0.3G/S: ≤3m³
Discharge Time ≤14s
Discharge Delay Time ≤0.5s
Nozzle Thermal Clearance Temperature at 400mm from nozzle ≤75℃
Surface Temperature of Enclosure ≤75℃
Extinguishing Density 100g/m³~130g/m³
Service Life 6 Years
Protected Area Requirements Protected area should be relatively enclosed
Installation Method 3M adhesive, strong magnetic adsorption, screw fixation
Operating Environment -40~+85℃, <95%RH
Activation Method Temperature-based activation:
(when any point of thermal detection line exceeds 170℃)
Logical activation (temperature exceeds 100℃ and smoke detected simultaneously)
Remote activation (via host or cloud platform)
Manual forced start (emergency button, press and hold for 3 seconds)
Over-temperature activation (when any point of thermal detection line exceeds 170℃)

Frequently Asked Questions (FAQ)

How is the QRR series fire extinguishing device activated?

Depending on the model, activation methods include thermal detection line over-temperature activation (exceeding 170℃), logical multi-sensor activation (simultaneous >100℃ temperature and smoke detection), remote activation via software/cloud, or manual forced start by pressing the emergency button for 3 seconds.

Can the device be reused after it discharges?

Yes. The product features a two-segment modular structure. After a discharge event, the extinguishing cartridge can be easily replaced independently, allowing the device to be reused and significantly lowering maintenance costs.

What are the available installation options?

The device offers flexible mounting options to suit various environments, including industrial-grade 3M adhesive, high-strength magnetic adsorption, and secure screw fixation.

What are the differences between the MR1, MR2, MR3, and MR4 models?

The primary difference is the communication method: MR1 is a standalone unit without networking; MR2 supports RS485 wired connections; MR3 uses LoRa wireless connectivity; and MR4 is equipped with 4G wireless capabilities for direct cloud interaction and app management.

What size area can each unit protect?

The 0.1G/S unit is designed to protect spaces up to 1 m³, while the 0.3G/S unit protects enclosures up to 3 m³. The protected space should remain relatively sealed to ensure maximum fire suppression performance.