ODM SG/ZSG/SBK Series Three-Phase Dry-Type (Rectifier) Transformer Supplier, Manufacturers

The SG series three-phase dry-type transformers are widely used in CNC systems, suitable for various three-phase power supply applications with AC 50~60Hz and input/output voltages not exceeding 500V. Customization options include input/output voltage levels, connection groups, number and position of tapping taps (usually ±5%), distribution of winding capacities, configuration of secondary single phase windings, integration of rectifier circuits, and requirements for external enclosures. All designs can be meticulously manufactured according to user specifications. The ZSG series three-phase dry-type rectifier transformers are designed for rectifier equipment, used for charging, voltage regulation, and DC power supply after rectification.

Product Description

Type & Meaning

SG Type Dry-type Transformer Designation
SThree-phase
GDry-type Transformer
□Rated Capacity (kVA)
□Voltage Class (kV)
ZSG Rectifier Transformer Designation
ZRectifier
SThree-phase
GDry-type Transformer
□Rated Capacity (kVA)
□Voltage Class (kV)
SBK Control Dry-type Transformer Designation
SThree-phase
BKDry-type Transformer
□Rated Capacity (kVA)
□Voltage Class (kV)

Product Display

Outline and Installation Dimensions

The outline and installation dimension drawings of SG, ZSG, and SBK are shown in the following table and Figures 1, 2, and 3:

Outline and Mounting Dimensions Schematic 1
Model Output Voltage Connection Group Number Overall Dimensions (mm) Mounting Dimensions K×J
Input Output Open Type Protected Type Open Type Protected Type
Bmax Dmax Emax Bmax Dmax Emax A±5 C±5 A±5 C±5
SG, ZSG, SBK-0.15KVA 660
400
380
200
380
220
110
36
Y/yn(oY/Yo)
Y/d(Y/△)
D/y(△/Y)
Y/d(△/△)
20010514026018016012577 8×18
SG, ZSG, SBK-0.3KVA 1801101802601801607570
SG, ZSG, SBK-0.5KVA 1801151802602001207575
SG, ZSG, SBK-0.75KVA 23013020026025026011085
SG, ZSG, SBK-1KVA 23014020031520026011090
SG, ZSG, SBK-1.5KVA 230155200355290280110105 10×12
SG, ZSG, SBK-2KVA 270165250180130
SG, ZSG, SBK-2.5KVA 270175250370290300180140
SG, ZSG, SBK-3KVA 270185250180150
SG, ZSG, SBK-4KVA 300180285510400550200140420220
SG, ZSG, SBK-5KVA 300200285200155
SG, ZSG, SBK-10KVA 370210240560430600265160470230
SG, ZSG, SBK-15KVA 420245390600440620310180580240
SG, ZSG, SBK-20KVA 540320450650440650340185770300 Φ12
SG, ZSG, SBK-30KVA 540380480870500780340210
SG, ZSG, SBK-40KVA 750350520960550810420170870350
SG, ZSG, SBK-50KVA 180
SG, ZSG, SBK-60KVA 8004506501000810810420195900350
SG, ZSG, SBK-80KVA 205
SG, ZSG, SBK-100KVA 8604506501050810810420220960350
SG, ZSG, SBK-125KVA 860500700
SG, ZSG, SBK-160KVA 950600800
SG, ZSG, SBK-200KVA 1000680850
SG, ZSG, SBK-250KVA 1050700850

Note:

1. Dimensions not specified in blanks are to be determined per user requirements and are for reference only. Products with output current exceeding 3000A are custom-positioned, with dimensions corresponding to their specifications.

2. The rated input and output voltages listed in the table can be freely combined as required.

3. The voltages and dimensions listed in the table can be negotiated and determined according to user requirements.

Outline and Mounting Dimensions Schematic 2

Frequently Asked Questions

What are the primary differences between SG, ZSG, and SBK transformers?

SG represents standard three-phase dry-type transformers, ZSG is engineered specifically as a rectifier transformer system, and SBK functions primarily as an industrial control dry-type transformer.

Can the input and output voltages be customized for specific grid requirements?

Yes. The standard listed input (660V, 400V, 380V, 200V) and output (380V, 220V, 110V, 36V) configurations can be combined freely or fully customized to meet site-specific engineering requirements.

What is the difference between Open Type and Protected Type enclosures?

Open Type units are designed for installation within enclosed electrical control cabinets without independent shielding. Protected Type units include an external enclosure that safeguards internal windings against environmental contaminants and contact hazards.

How are dimensions determined for high-capacity applications over 3000A?

For applications where the operating output current exceeds 3000A, products are custom-engineered. Dimensions, cooling clearances, and terminal placements will be determined directly based on the project specification sheet.

What standard connection group configurations are supported?

These series support standard vector wiring schemes including Y/yn (oY/Yo), Y/d (Y/△), D/y (△/Y), and Y/d (△/△) to match varying phase balance and harmonic requirements.

Related Products