ODM HR17 Fused Isolation Switch For High Current Suppliers, Companies

The HR17 Fused Isolation Switch delivers robust circuit protection and isolation for industrial power systems, supporting 40A-800A loads at AC400-1000V with 1000V insulation and 12kV impulse withstand. This fused isolation switch complies with AC-21B/22B/23B utilization categories, ensuring reliable performance for motor control and resistive loads. Featuring 50kA short-circuit current rating (105kA peak) and low phase-breaking power consumption (5-48W), the HR17 switch combines fused protection with manual isolation in one compact unit. Ideal for high-voltage applications, it provides visible disconnect assurance and meets IEC60947-3 standards for industrial safety and durability.

Product Description

Type and Meaning

HR3-10
No. Meaning / Designation
1 Fuse-type isolating switch
2 Design serial number
3 Conventional heating current
4 Number of poles: 2P, 3P, 4P
5 "1" indicates with auxiliary contacts;
"0" indicates without auxiliary contacts
6 "C" indicates fixed type;
"T" indicates plug-in type
7 "D" indicates with a disconnecting blade

Product Display

Technical Parameters

Specification 40 100(63) 160(100) 250 400 630 800
Rated Working Voltage (Ue) 1000V a.c
400V a.c
Rated Insulation Voltage (Ui) 1000V
Rated Impulse Withstand Voltage (Uimp) 12kV
Rated Working Current (Ie) AC400V AC-21B 40A 63,100A 100,160A 250A 400A 630A 800A
AC-22B 40A 63,100A 100,160A 250A 400A 630A 800A
AC-23B 40A 63,100A 100,160A 250A 400A 630A 800A
AC1000V AC-21B - - 100,160A 250A 400A 630A 800A
AC-22B - - 100A 160A 400A 630A 800A
Rated Short-circuit Current 50kA (Peak 105kA)
The Phase-breaking Power Consumption under IEC60947-3 Standard 5 9.5 12 23 34 48 48

Outline and Installation Dimension

HR17-40-800A Fixed Type
HR3-4 Fixed Type Dimension
Model Number of Poles Outline Dimensions (mm) Installation Dimensions (mm)
A B C D a b Φc
HR17-40 2P 55 116 76 150 25 - Φ6
3P 76 116 76 150 42 - Φ6
HR17-100 3P 105 116 76 150 62 - Φ6
HR17-160 3P 106 200 83 205 66 25 Φ7
4P 138 200 83 205 100 25 Φ7
HR17-250 3P 185 247 110 295 114 50 Φ11
4P 242 247 110 295 172 50 Φ11
HR17-400 3P 210 290 125 340 130 50 Φ11
4P 276 290 125 340 195 50 Φ11
HR17-630 3P 256 300 145 360 162 50 Φ11
4P 340 300 145 360 243 50 Φ11
HR17-800 3P 256 300 145 360 162 50 Φ11
4P 340 300 145 360 243 50 Φ11
HR17-160-800A Plug-in Type
HR3-4 Plug-in Type Dimension
Model A B C D E F
HR17-160/30 106 200 97 60 200 87
HR17-250/30 185 247 128 88 221 110
HR17-400/30 210 290 145 97 268 125
HR17-630/30 256 300 160 112 285 139
HR17-800/30 256 300 160 112 285 139

Frequently Asked Questions

What is the rated voltage range of the HR17 series fuse-type isolating switch?

The HR17 series operates at a rated working voltage (Ue) of AC 400V and AC 1000V, with a rated insulation voltage (Ui) up to 1000V and an impulse withstand voltage (Uimp) of 12kV.

What pole configurations are available for this series?

Depending on the specific current rating and installation requirement, the series is available in 2-pole (2P), 3-pole (3P), and 4-pole (4P) designs.

What are the main installation types for the HR17 switch?

The switch provides two mounting structures: Fixed Type (indicated by "C") covering 40A to 800A ratings, and Plug-in Type (indicated by "T") covering 160A to 800A ratings.

What is the rated short-circuit capacity of the HR17 series?

The switch provides high protection performance with a rated short-circuit current of 50kA and peak short-circuit withstand capability up to 105kA.

Can auxiliary contacts be integrated into the unit?

Yes, units can be designated with auxiliary contacts ("1" in the model code indicates configuration with auxiliary contacts, while "0" indicates without auxiliary contacts).

Does the product meet international electrical standards?

Yes, performance specifications including phase-breaking power consumption comply strictly with the IEC60947-3 low-voltage switchgear and controlgear standard.