High-Quality SJK47LE-63 Residual Current Circuit Breaker RCCB Companies, Company

The SJK47LE-63 Residual Current Circuit Breaker (RCCB) provides reliable earth leakage and overcurrent protection for 230V/400V AC systems (50Hz). Available in 1P, 2P, 3P, and 4P configurations with current ratings from 6A to 63A, this RCCB features C/D-type tripping characteristics and withstands short-circuit currents up to 6000A. Ideal for residential and commercial applications, the SJK47LE-63 RCCB ensures safety against electrical faults while maintaining stable performance in 30°C–35°C environments. Compliant with international standards, it combines compact design with robust protection.

Product Description

Type Designation

DZ47LE-63-6 Type Designation
Position Description
1 Manufacturer Code
2 Design Serial Number
3 With Residual Current Protection (Earth Leakage Protection)
4 Rated Current Collection (32A, 63A)
5 Operational Current
6 Number of Poles

Product Display

Technical Parameters

Table 1
Maximum Frame-rated Current (A) Number of Poles With Neutral Pole Rated Current In (A) Rated Voltage Un (V) Rated Residual Operating Current I△n (mA) Rated Residual Non-operating Current I△no (mA) Breaking Time at I△n (s) Rated Residual Making & Breaking Capacity I△m (A) Instantaneous Overcurrent Release Type
32 1 +N 6
10
16
20
25
230 30
50
100
300
15
25
50
150
<0.1 2000 C
D
2 - 230
3 - 400
3 +N 400
4 - 400
63 1 +N 32
40
50
63
230
2 - 230
3 - 400
3 +N 400
4 - 400

◇ Rated Short-Circuit Capacity (Icn), Service Short-Circuit Breaking Capacity (Ics)

Table 2
Model Rated Current Rated Short-Circuit Current (A) Operating Short-Circuit Breaking Capacity (A)
SJK47LE 6~63A 4500 4500
SJK47LEH 6~63A 6000 6000

◇ Overcurrent Protection Characteristics at 30°C~35°C (Ref. Table 3)

Table 3
No. Rated Current of Release (A) Initial State Test Current Specified Time Expected Result Notes
1 6~63 Cold State 1.13In t ≤ 1h (In ≤ 63A) No Tripping -
2 6~63 Immediately after previous test 1.45In t < 1h (In ≤ 63A) Tripping Current rises steadily to specified value within 5s
3 In ≤ 32 Cold State 2.55In 1s < t < 60s Tripping -
In > 32 Cold State 2.55In 1s < t < 120s Tripping -
4 6~63 Cold State 5In
10In
t ≤ 0.1s
t < 0.1s
No Tripping
Tripping
C Type
10In
14In
t ≤ 0.1s
t < 0.1s
No Tripping
Tripping
D Type

◇ Wiring: For conductors ≤25mm² (Ref. Table 4). Connection method: Screw-clamp terminals, Torque 2N·m

Table 4
Rated Current In (A) Nominal Cross-Sectional Area of Copper Conductor (mm²)
6 1
10 1.5
16, 20 2.5
25 4
32 6
40, 50 10
63 16

Outline and Installation Dimensions

DZ47LE-63-4 Outline Dimensions
Table 5
1P+N 2P 3P 3P+N 4P
18+36 mm 36+36 mm 54+54 mm 54+72 mm 72+72 mm

Frequently Asked Questions (FAQ)

What is the primary function of the SJK47LE-63 series circuit breaker?
The SJK47LE-63 is a residual current circuit breaker with overcurrent protection (RCBO). It provides protection against earth leakage faults, short circuits, and overload conditions in low-voltage electrical distribution networks.
What is the difference between SJK47LE and SJK47LEH models?
The main difference lies in their breaking capacity. The SJK47LE model provides a rated short-circuit breaking capacity of 4,500A (4.5kA), whereas the high-breaking capacity version SJK47LEH is rated for up to 6,000A (6kA).
What instantaneous tripping curves are available?
This product series offers both C-type and D-type tripping curves. Type C (tripping at 5–10In) is standard for residential and commercial lighting loads, while Type D (tripping at 10–14In) is designed for inductive industrial equipment with high starting surge currents.
What is the residual operating current (I△n) sensitivity?
The residual current ratings range from standard human-safety protection (30mA) up to equipment protection levels (50mA, 100mA, and 300mA), all operating within a rapid breaking time of less than 0.1 seconds.
What conductor sizes and screw tightening torque are recommended?
The device features standard screw-clamp terminals suitable for copper conductors up to 25mm² (ranging from 1mm² for 6A loads up to 16mm² for 63A loads) with a recommended tightening torque of 2 N·m.