This SJKS1D series surge protection device (SPD) safeguards electrical systems against lightning and transient surges, with no need for power shutdown during unit replacement. Rated for 420V continuous operation, it handles up to 20kA (8/20μs) peak currents and responds in under 25ns for ultra-fast protection. A clear visual indicator shows green for normal operation and red for faults. Available in 1P–4P modular units, it fits standard 35mm DIN rails and works reliably from -40°C to +85°C, ideal for industrial, commercial, and residential applications.

Product Description

Type Designation

SJKS1D
1 Surge Protective Device (SPD)
2 Class D Protection
3 Maximum Discharge Current Imax (kA)
4 Number Of Poles: 1P, 2P, 3P, 4P, N+PE
5 Maximum Continuous Operating Voltage Uc (V)

Product Features

✔
Protector unit can be replaced without power interruption.
✔
Withstands lightning current surges up to 20kA (8/20μs).
✔
Response time: < 25 ns.
✔
Visual indicator window shows protection status: Green = Normal, Red = Fault.

Product Display

Technical Parameters

Parameter SJKS1-10 SJKS1-20
Maximum continuous operating voltage Uc (V~) 420V
Voltage protection level Up (V~, kV) ≤1.0 ≤1.2
Nominal discharge current In (8/20μs, kA) 5kA 10kA
Maximum discharge current Imax (8/20μs, kA) 10kA 20kA
Response time (ns) <25
Connection cross-section L/N (mm²) 6mm²
Connection cross-section PE (mm²) 10mm²
Recommended fuse / breaker rating (A) 10A, 16A
Operating temperature (°C) -40°C ~ +85°C
Relative humidity (at 25°C) ≤95%
Mounting Standard 35mm DIN rail
Housing material Glass fiber reinforced plastic

Outline Dimensions and Installation Size

Here’s the standardized English version for your SJKS1D Series Surge Protection Device, including common dimensions based on DIN rail SPD form factors:

SJKS1D-3
Poles Width Height Total Depth Mounted Depth Housing Height DIN Rail Width
1P 18 90 62 50 45 35
2P 36 90 62 50 45 35
3P 54 90 62 50 45 35
4P 72 90 62 50 45 35

Frequently Asked Questions

Can the protection module be replaced while the system is powered on?
Yes, the protector unit is designed with a pluggable architecture that allows for replacement without power interruption, ensuring continuous electrical operation and safety.
What does the visual indicator window indicate?
The status window provides clear visual monitoring: Green signifies normal operation, while Red indicates a fault state, signalling that the module needs to be replaced.
How quickly does the surge protective device react to electrical surges?
The device features an ultra-fast response time of less than 25 nanoseconds (<25 ns), delivering rapid suppression against lightning surges and transient overvoltages.
What mounting system is required for installation?
The SJKS1D series is engineered for tool-free, modular installation on standard 35mm DIN rails, making it compatible with standard distribution boards.
What is the difference between SJKS1-10 and SJKS1-20 models?
The SJKS1-10 handles a nominal discharge current of 5kA with a max rating of 10kA (Up ≤1.0 kV), whereas the SJKS1-20 offers higher protection capacity with a nominal current of 10kA and max current of 20kA (Up ≤1.2 kV).