ODM SJKQ2Z ATS Switch Dual Power For LV Power Manufacturers, Factory

The SJKQ2Z ATS Automatic Transfer Switch integrates seamlessly with SJKM1 series circuit breakers to provide reliable power switching for 100A-1250A loads at 400V AC/50-60Hz. Designed for critical backup systems, this ATS features adjustable delay timing (0-30s), 2500V insulation withstand, and 5000-cycle mechanical endurance. With 3P/4P configurations and AC230V control voltage, the SJKQ2Z Automatic Transfer Switch ensures smooth transitions between primary and secondary sources while preventing flicker or breakdown. Ideal for industrial and commercial applications, it combines robust construction with intelligent monitoring for uninterrupted power distribution.

Product Description

Type Designation

Q2Z ATS Switch Dual Power Type Designation
Index Designation Breakdown
1 Manufacturer Code
2 Auto-Transfer Function
3 Derivative Code:
(): MCCB; W: Compact Type; W1: Economy Type; W2: Smart Type (Undervoltage / Phase-Loss / Off / Fire Protection)
4 Function Code:
R: Grid-to-Grid (Optional); F: Grid-to-Generator; M: Terminal Type (Optional);
Y: Integrated Smart Type (Off / Fire Protection / Undervoltage); N: Split Smart Type (Off / Fire Protection / Undervoltage)
5 Frame Size Current
6 Number of Poles
7 Rated Current (In)

Setting Program Instructions

SJKQ2Z Controller Interface
  • 1. LCD Display
  • 2. SET Button
  • 3. Right-Shift Button
  • 4. Increment Button (+)
  • 5. Decrement Button (-) / Alarm
  • 6. Manual Mode Button
  • 7. Auto Mode Button
  • 8. Dual-Off Button
Note: LCD display abbreviations: "Auto-reclose" (AR), "No auto-reclose" (NAR). "SF01" must not be changed.
Step Key Press Display Operation Description Functionality
1 SET CodE Enter setting mode Password setup
2 >> OodE Press (︽ ︾) to set the first digit Password setup
3 >> 80dE Press (︽ ︾) to set the second digit Password setup
4 >> 880E Press (︽ ︾) to set the third digit Password setup
5 >> 8888 Press (︽ ︾) to set the fourth digit Password confirmation (8888)
6 >> dddd / N-R 03s Correct password verified; Displays Normal-Backup transfer time Normal-Backup transfer time
Press (︽ ︾) to configure N-R 1st-stage delay
7 >> N-R 03s Displays Normal-Backup transfer time Normal-Backup transfer time
Press (︽ ︾) to configure N-R 2nd-stage delay
8 >> R-N 03s Displays Backup-Normal transfer time Backup-Normal transfer time
Press (︽ ︾) to configure R-N 1st-stage delay
9 >> R-N 03s Displays Backup-Normal transfer time Backup-Normal transfer time
Press (︽ ︾) to configure R-N 2nd-stage delay
10 >> SF 08s Displays dual-off time Dual-off transfer time
Press (︽ ︾) to configure SF 1st-stage delay
11 >> SF 08s Displays dual-off time Dual-off transfer time
Press (︽ ︾) to configure SF 2nd-stage delay
12 >> FFF 1 Press (︽ ︾) to set auto-recovery (1=ON, 0=OFF) Auto-recovery toggle
13 >> FD 0 Press (︽ ︾) to set generator mode (0=Full-auto, 1=Semi-auto) Generator control
14 >> FC 0 Press (︽ ︾) to configure priority (0=Normal, 1=Backup) Priority configuration
15 >> H 130 Press (︽ ︾) to configure Overvoltage threshold (220V * 130%) Overvoltage protection
16 >> L 50 Press (︽ ︾) to configure Undervoltage threshold (220V * 50%) Undervoltage protection
17 >> NA 220V Press (︽ ︾) to calibrate Normal Phase-A voltage Live voltage calibration
18 >> NB 220V Press (︽ ︾) to calibrate Normal Phase-B voltage Live voltage calibration
19 >> NC 220V Press (︽ ︾) to calibrate Normal Phase-C voltage Live voltage calibration
20 >> RA 220V Press (︽ ︾) to calibrate Backup Phase-A voltage Live voltage calibration
21 >> RB 220V Press (︽ ︾) to calibrate Backup Phase-B voltage Live voltage calibration
22 >> RC 220V Press (︽ ︾) to calibrate Backup Phase-C voltage Live voltage calibration
23 >> SAVE Press to apply and store settings Save configuration

Product Display

Technical Parameters

Model Circuit Breaker Model Frame Size Current (A) Rated Operational Current (In)
SJKQ2Z-100/3 SJKM1 Series 100 10 / 16 / 20 / 25 / 32 / 40 / 50 / 63 / 80 / 100
SJKQ2Z-100/4
SJKQ2Z-225/3 225 100 / 125 / 140 / 160 / 180 / 200 / 225
SJKQ2Z-225/4
SJKQ2Z-400/3 400 250 / 315 / 350 / 400
SJKQ2Z-400/4
SJKQ2Z-630/3 630 400 / 500 / 630
SJKQ2Z-630/4
SJKQ2Z-800/3 800 630 / 700 / 800
SJKQ2Z-800/4
SJKQ2Z-1250/3 1250 800 / 1000 / 1250
SJKQ2Z-1250/4
Breaking Current (kA) Refer to the instruction manual of the specific circuit breaker model.
Rated Operational Voltage (V) 400V
Insulation Voltage (V) 2500V (No flicker and no breakdown within 1 minute)
Frequency (Hz) 50 - 60 Hz
Delay Time 0 ~ 30s (Adjustable)
Control Rated Operating Voltage (V) AC 230V
Mechanical Life 5,000 Operations

Outline and Installation Dimensions

Installation Dimensions Diagram
Model Dimensions W (mm) W1 (mm) L (mm) L1 (mm) H (mm)
SJKQ2Z-100/3P390355220200120
SJKQ2Z-100/4P420385220200120
SJKQ2Z-225/3P430395220205140
SJKQ2Z-225/4P465435220205140
SJKQ2Z-400/3P560510310285190
SJKQ2Z-400/4P605555310285190
SJKQ2Z-630/3P625570320295195
SJKQ2Z-630/4P690635320295195
SJKQ2Z-800/3P705655340315190
SJKQ2Z-800/4P780730340315190
SJKQ2Z-1250/3P730675480365280
SJKQ2Z-1250/4P800745480365280

Installation and Usage Instructions

Terminal Wiring Diagram
  • 21: Normal Neutral Line
  • 22: Alternate Neutral Line
  • 23, 24: Normal Source ON Indicator Light
  • 25, 26: Alternate Source ON Indicator Light
  • 27, 28: Normal Source ON Indicator Light
  • 29, 30: Alternate Source ON Indicator Light
  • 31, 32: Duo Status Indicator Light
  • 33, 34: Fire Signal Input / AC or DC 6-24V Dry Contact
  • 35, 36: Generator Contact (5A)

Frequently Asked Questions (FAQ)

What is the default setup password for the SJKQ2Z ATS controller?
The controller setup password is set to 8888. Enter this code step-by-step using the shift and increment keys to access programmable operating parameters.
Can the transfer delay time be customized?
Yes, both Normal-to-Backup and Backup-to-Normal transfer times feature fully adjustable multi-stage delay settings within a range of 0 to 30 seconds.
How does the ATS interface with an emergency standby generator?
The switch provides dedicated generator start contacts (terminals 35 & 36, rated at 5A) and can be set to either full-automatic (FD 0) or semi-automatic (FD 1) modes via the control interface.
Does this automatic transfer switch support fire protection integration?
Yes, smart models support emergency fire linkage using terminals 33 & 34, compatible with an AC or DC 6-24V dry contact input to automatically execute a dual-off release when triggered.
What frame current ratings are available in this series?
The series offers frame sizes ranging from 100A up to 1250A across 3-Pole and 4-Pole configurations, covering rated operational currents from 10A to 1250A.