High-Quality GCS Low Voltage Withdrawable Switchgear Panel for Power Distribution Factories, Company

CS low-voltage withdrawable switchgear is suitable for distribution systems in industries such as power plants, petroleum, chemical, metallurgical, textile, and high-rise buildings. In places with high automation levels such as large power plants and petrochemical systems that require computer interfaces, this low-voltage complete distribution device is used for power distribution, centralized control of electric motors, and reactive power compensation in power generation and supply systems with a three-phase AC frequency of 50 (60) Hz, rated operating voltage of 380V (400V), (660V), and rated current of 4000A or below.

Product Description

Type Designation

GCS-Low-Voltage-Withdrawable-Switchgear-Panel-8
1 Enclosed switchgear
2 Withdrawable switchgear
3 Electrical System
4 Main circuit scheme number
5 Auxiliary circuit scheme number

Technical Parameters

Main circuit Rated Voltage (V) AC 380(400),(660)
Auxiliary circuit Rated Voltage (V) AC 220, 380(400) / DC 110, 220
Rated Frequency (Hz) 50(60)
Rated Insulation Voltage (V) 660(1000)
Rated Current (A) Horizontal Busbar ≤4000
Vertical Busbar (MCC) 1000
Busbar Rated Short-Time Withstand Current (kA/1s) 50, 80
Busbar Rated Peak Withstand Current (kA/0.1s) 105, 176
Power-Frequency Withstand Voltage (V/1min) Main circuit 2500
Auxiliary circuit 1760
Busbar System 3-Phase 4-Wire System A.B.C.PE.N
3-Phase 5-Wire System A.B.C.PE.N
Operating Mode / Protection Degree IP30, IP40

Product Display

GCS-Low-Voltage-Withdrawable-Switchgear-Panel-(1)
GCS-Low-Voltage-Withdrawable-Switchgear-Panel-(2)

Figure 1. Installation Drawing

GCS-3
H 2200
W 400 600 800 1000
D 800 1000 800 1000 600 800 1000 600 800 1000
General Cabinet Code A B C D Notes
GCS-TG1010-4 1000 1000 850 956 Tie Cabinet
GCS-TG0810-4 800 1000 650 956 Incoming Cabinet
GCS-TG0808-4 800 800 650 756 Incoming Cabinet
GCS-TG0608-4 600 800 450 756 Incoming Cabinet

Figure 2. PC Cabinet Installation Schematic

GCS-6
General Cabinet Code A B C D E F×G
GCS-TG1010-2 1000 1000 850 956 60 400×400
GCS-TG0810-2 800 1000 650 956 160 200×400
GCS-TG1008-2 1000 800 850 756 60 400×400
GCS-TG0808-2 800 800 650 756 160 200×400

Figure 3. MCC Cabinet Installation Schematic

GCS-8
General Cabinet Code A B C D E F×G
GCS-TG1006-1 1000 600 850 556 60 400x350
GCS-TG0806-1 800 600 650 556 160 200x350

Ordering Notice

Product operating site and special requirements:

1. Provide product ordering drawings, which should include wiring diagrams and indicate transformer capacity, main component model specifications, distribution branch circuits, and capacity.

2. When it is necessary to configure electric energy metering and reactive power automatic compensation devices, the requirements for the configuration of the metering meter and transformer should be provided, and the capacity of the compensation capacitor should be indicated.

3. Specify the requirements for surface treatment of the product.

Frequently Asked Questions (FAQ)

What is the rated voltage range for this switchgear?

The main circuit rated voltage is AC 380V (400V), (660V), and the auxiliary circuit rated voltage supports AC 220V, 380V (400V) as well as DC 110V, 220V.

What is the maximum rated current capacity for the busbars?

The horizontal busbar supports a rated current of up to ≤4000A, while the vertical busbar (MCC) supports a rated current of 1000A.

What ingress protection (IP) ratings are available?

The switchgear provides operational protection degrees of IP30 and IP40 depending on configuration requirements.

Which busbar wire systems are compatible?

The switchgear is compatible with both 3-Phase 4-Wire and 3-Phase 5-Wire systems (A.B.C.PE.N).

What documents are required when placing an order?

Ordering requires product drawings including wiring diagrams, transformer capacity, main component models, distribution branch circuits, reactive power compensation details (if required), and specified surface treatment preferences.