OEM SJK47LE-63 RCCB: Reliable Earth Leakage Protection from China Suppliers and Factory for 230V/400V AC Systems Supplier, Factories

,

Introducing the SJK47LE-63 Residual Current Circuit Breaker (RCCB), a top choice among China suppliers and factories for reliable earth leakage and overcurrent protection in 230V/400V AC systems (50Hz). This versatile RCCB comes in 1P, 2P, 3P, and 4P configurations, with current ratings ranging from 6A to 63A. Featuring C/D-type tripping characteristics, it can withstand short-circuit currents of up to 6000A, making it ideal for both residential and commercial applications. The SJK47LE-63 RCCB ensures safety against electrical faults while delivering stable performance in temperatures between 30°C and 35°C. Designed to meet international standards, this compact yet robust device is your go-to solution for electrical safety.

,

Product Description

Type Designation

Type Designation Guide
  • 1Manufacturer Code
  • 2Design Serial Number
  • 3With Residual Current Protection (Earth Leakage Protection)
  • 4Rated Current Collection (32A, 63A)
  • 5Operational Current
  • 6Number of Poles

Product Display

SJK47LE-63 Residual Current Circuit Breaker Front View
SJK47LE-63 Residual Current Circuit Breaker Perspective
SJK47LE-63 Residual Current Circuit Breaker Top Angle
SJK47LE-63 Residual Current Circuit Breaker Terminals

Technical Parameters

Table 1: Main Specifications
Maximum Frame-rated Current (A) Number of Poles With Neutral Pole Rated Current In (A) Rated Voltage Un (V) Rated Residual Operating Current I△n (mA) Rated Residual Non-operating Current I△no (mA) Breaking Time at I△n (s) Rated Residual Making & Breaking Capacity I△m (A) Instantaneous Overcurrent Release Type
32 1 +N 6
10
16
20
25
230 30
50
100
300
15
25
50
150
<0.1 2000 C
D
2 230
3 400
3 +N 400
4 400
63 1 +N 32
40
50
63
230
2 230
3 400
3 +N 400
4 400
◇ Rated Short-Circuit Capacity (Icn), Service Short-Circuit Breaking Capacity (Ics).
Table 2: Short-Circuit Capacity
Model Rated Current Rated Short-Circuit Current (A) Operating Short-Circuit Breaking Capacity (A)
SJK47LE 6~63A 4500 4500
SJK47LEH 6~63A 6000 6000
◇ Overcurrent Protection Characteristics at 30°C~35°C (Ref. Table 3)
Table 3: Overcurrent Tripping Characteristics
No. Rated Current of Release (A) Initial State Test Current Specified Time Expected Result Notes
1 6~63 Cold State 1.13In t≤1h  In≤63A No Tripping
2 6~63 Immediately after previous test post-test condition 1.45In t<1h  In≤63A Tripping Current Rises Steadily to Specified Value Within 5s
3 In≤32 Cold State 2.55In 1s<t<60s Tripping
In>32 Cold State 2.55In 1s<t<120s Tripping
4 6~63 Cold State 5In
10In
t≤0.1s
t<0.1s
No Tripping
Tripping
C Type
10In
14In
t≤0.1s
t<0.1s
No Tripping
Tripping
D Type
◇ Wiring: For conductors ≤25mm² (Ref. Table 4)   Connection method: Screw-clamp terminals, Torque 2N·m
Table 4: Recommended Conductor Cross-Section
Rated Current In (A) Nominal Cross-Sectional Area of Copper Conductor (mm²)
61
101.5
16、202.5
254
326
40、5010
6316

Outline and Installation Dimensions

Outline and Installation Dimensions Diagram
Table 5: Dimensional Data
1P+N 2P 3P 3P+N 4P
18+36 36+36 54+54 54+72 72+72

Frequently Asked Questions

Q What is the difference between the SJK47LE and SJK47LEH models?
The SJK47LE has a rated short-circuit current (Icn) and operating short-circuit breaking capacity (Ics) of 4500A, while the SJK47LEH is a higher-capacity version rated at 6000A for both values. Both models cover the same current range of 6~63A.
Q What residual current (earth leakage) settings are available for the SJK47LE-63?
The SJK47LE-63 supports four rated residual operating current (I△n) settings: 30mA, 50mA, 100mA, and 300mA. The corresponding rated residual non-operating currents (I△no) are 15mA, 25mA, 50mA, and 150mA respectively. The breaking time at I△n is less than 0.1 seconds.
Q What is the difference between C Type and D Type instantaneous overcurrent release?
C Type trips instantaneously when the current reaches 10In (does not trip at 5In within 0.1s). D Type trips instantaneously when the current reaches 14In (does not trip at 10In within 0.1s). C Type is suitable for general residential and light commercial loads, while D Type is designed for equipment with high inrush currents such as motors and transformers.
Q What copper conductor cross-sectional area should be used with a 63A rated current?
For a rated current of 63A, a copper conductor with a nominal cross-sectional area of 16mm² is recommended. The connection method uses screw-clamp terminals with a tightening torque of 2N·m. Conductors up to 25mm² are supported.
Q What pole configurations are available for the SJK47LE-63?
The SJK47LE-63 is available in 1P+N, 2P, 3P, 3P+N, and 4P configurations. Single-pole and 2-pole variants are rated at 230V, while 3-pole, 3P+N, and 4-pole variants are rated at 400V.
Q What are the overcurrent protection characteristics of the SJK47LE-63 under normal temperature conditions?
At 30°C~35°C ambient temperature: the breaker will not trip at 1.13In for up to 1 hour (cold state); it will trip within 1 hour at 1.45In (immediately following the previous test). At 2.55In from cold state, breakers rated ≤32A trip within 1s~60s, and those rated >32A trip within 1s~120s.