High-Quality China SJKM8 MCCB Suppliers | 100A to 630A Moulded Case Circuit Breaker Factory for Reliable Circuit Protection Supplier, Companies

,

The SJKM8 Moulded Case Circuit Breaker (MCCB) is a high-performance solution for circuit protection in China, suitable for both 50Hz and 60Hz systems with insulation ratings up to 690V and current capacities ranging from 100A to 630A. This MCCB is available in various configurations including 1P, 2P, 3P, and 4P, making it a versatile choice for any panel integration. As one of the leading suppliers in the industry, we ensure that the SJKM8 MCCB adheres to IEC60947-2 and EN60947-2 standards, providing robust performance for industrial and commercial applications. Designed for optimal overload and short-circuit protection, this product is perfect for power distribution systems that demand high breaking capacity. Its compact design allows for space-saving installations without compromising on superior arc-quenching performance, making it an ideal choice for customers looking for reliable products from a reputable factory.

,

Product Description

Type Designation
SJKM8-Moulded-Case-Circuit-Breaker-6
1Manufacturer Code
2Molded Case Circuit Breaker Code
3Design Code
4Frame Size
5Short-Circuit Breaking Capacity Level 4
6Operation method 3
7Number of Poles 2
8Trip Unit Method & File Code
Technical Parameters
SJKM8 Series Circuit Breaker SJKM8-100 SJKM8E-160/250 SJKM8-160/250 SJKM8-400 SJKM8-630
Pole Number 1,2,3,4 3 3,4 3,4 3,4
Control Manual Toggle handle ■ ■ ■ ■ ■
Direct or extended rotary handle ■ ■ ■ ■ ■
Type Fixed Front connection ■ ■ ■ ■ ■
Rear connection - ■ ■ ■ ■
Plug-in Front connection ■ ■ ■ ■ ■
Rear connection - ■ ■ ■ ■
Electrical performance complies with IEC 60947-2 and EN 60947-2 standards
Rated Current (A) In 40℃ 100 160/250 160/250 400 630
Rated Insulation Voltage(V) Ui 690 690 690 690 690
Rated Impulse Withstand Voltage (kV) Uimp 6 6 6 6 6
Rated Working Voltage (V) Ue AC 50/60Hz 500 500 500 500 500
Circuit Breaker Type NHNHNHNHNH
Ultimate Breaking Capacity (kA rms) Icu AC 50/60Hz 220/240V 5065508550858510085100
380/400V 25352536253636503650
415V 25302536253636503650
440V 20202025202536503650
500V 101081081020362036
Service Breaking Capacity (kA rms) lcs AC 50/60Hz 220/240V 25302543254343504350
380/400V 13171318131818251825
415V 771318131818251825
440V 551013101318251825
500V 33454510181018
Isolation Function ■ ■ ■ ■ ■
Application Category A A A A A
Maximum Expected Maintenance Value (C-O Cycle) Mechanical 8500 10000 10000 6000 6000
Electrical 440V In 4000 5000 5000 1000 1000
Protection
Release Thermo-magnetic Thermo-magnetic Thermo-magnetic Thermo-magnetic Thermo-magnetic
Overload Protection Long-time Delay Ir(In×…) ■ ■ ■ ■ ■
Short-Circuit Protection Short-time Delay Isd(In×…) - - - - -
Instantaneous li(In× ·) ■ ■ ■ ■ ■
Leakage Protection Circuit Breaker with Complete Leakage Protection - - ■ ■ ■
Vigirex Relay ■ ■ ■ ■ ■
Indication and Control Auxiliaries
Auxiliary Contact (FZ) and Alarm Contact (BJ) ■ ■ ■ ■ ■
Auxiliary Alarm Contact (FZ/BJ) ■ ■ ■ ■ ■
Shunt Trip Coil (FL) ■ ■ ■ ■ ■
Under-Voltage Coil (QY) ■ ■ ■ ■ ■
Modbus Communication
Pm200 Meter Electrical Measurement (Current, Voltage, Power, Energy) ■ ■ ■ ■ ■
Mc Multi-Circuit Monitoring Unit Status ■ ■ ■ ■ ■
Electrical Measurement (Current, Voltage) ■ ■ ■ ■ ■
Installation
Accessories Terminal Expansion and Extension ■ ■ ■ ■ ■
Terminal Cover ■ ■ ■ ■ ■
Phase Separator ■ ■ ■ ■ ■
Circuit Breaker Type N/H N/H N/H N/H N/H
Dimensions (mm) W×H×D Fixed Front Connection 1P 25×130×60 - - - -
Fixed Front Connection 2P 50×130×60 - - - -
Fixed Front Connection 3P 75×130×60 105x165x60 105x165×68 140x257x103 140×257x103
Fixed Front Connection 4P 100×130×60 - 140x165x68 185×257x103 185x257x103
Weight (kg) Fixed Front Connection 1P/2P 0.28/0.48 - - - -
Fixed Front Connection 3P/4P 0.78/1.0 1.3 1.6/2.1 6.05/7.9 6.5/8.7
Product Display
SJKM8-MCCB-(5)
SJKM8-Moulded-Case-Circuit-Breaker-(1)
SJKM8-Moulded-Case-Circuit-Breaker-(2)
SJKM8-Moulded-Case-Circuit-Breaker-(3)
SJKM8-Moulded-Case-Circuit-Breaker-(4)
SJKM8-Moulded-Case-Circuit-Breaker-(5)
Ambient Temperature
SJKM8-100~630
Rated current Environmental temperature
(A) 40℃45℃50℃55℃60℃65℃70℃
1515.715.31514.74.614.213.8
2020.420.22019.919218.916.5
2525.725.32524.724.524.324.0
3031430.73029429.128.528.0
4040.94044039.538.037637.1
5052.15105049.348.147346.6
6061.860.96059.057.556.655.7
7576.87597573.570.469869.1
8082.28118078.577.375.776.1
10010310110099294.293.592.7
100106.8103.510096.492.788.884.7
125134.91301251198114.3108.5102.5
160170.9165.5160154.3148.3142.1135.6
175175168161154146138126
2002152076200192183.8175.1165.9
225243.5234.5225215.1204.8193.91823
250270.6260.5250239227521542026
250268260250240228218208
320342333320307291278266
350375364350336319305291
400428416400384364348332
400400390.538137143619349.2339.7
500500488.1476.2464.34524436.5424.6
63063065600585570550535
SJKM8-100 1P,2P Fixed-type Power Distribution and Motor Protection
SJKM8-4
  • ① Outline Dimensions
  • ② Chassis Installation
  • ③ DIN Rail Installation
  • ④ Front-of-Panel Opening (Small)
  • ⑤ Front-of-Panel Opening (Large)
SJKM8-100 3P,4P Fixed-type Power Distribution and Motor Protection
SJKM8-5
  • ① Outline Dimensions
  • ② Chassis Installation
  • ③ DIN Rail Installation
  • ④ Front-of-Panel Opening (Small)
  • ⑤ Front-of-Panel Opening (Large)
Frequently Asked Questions
Q What is the rated current range of the SJKM8 Series Moulded Case Circuit Breaker?
The SJKM8 Series MCCB covers a rated current range from 15A up to 630A at 40℃, with available frame sizes including SJKM8-100, SJKM8E-160/250, SJKM8-160/250, SJKM8-400, and SJKM8-630 to suit various power distribution and motor protection applications.
Q What international standards does the SJKM8 MCCB comply with?
The SJKM8 Series circuit breaker's electrical performance complies with IEC 60947-2 and EN 60947-2 standards, ensuring reliable and internationally recognized safety performance for industrial and commercial installations.
Q What is the maximum ultimate breaking capacity (Icu) of the SJKM8 MCCB?
The SJKM8 Series achieves a maximum ultimate breaking capacity (Icu) of up to 100kA rms at 220/240V AC for the H-type in the 400A and 630A frame sizes. At 380/400V, the maximum Icu reaches 50kA rms for H-type units in the 400A and 630A frames.
Q What installation types and connection methods are available for the SJKM8?
The SJKM8 supports both Fixed and Plug-in installation types, each with Front connection and Rear connection options. Control can be performed via a toggle handle or a direct/extended rotary handle, providing flexible installation solutions for different panel configurations.
Q Does the SJKM8 support Modbus communication and remote monitoring?
Yes. The SJKM8 Series supports Modbus communication through the Pm200 Meter for electrical measurements including current, voltage, power, and energy, as well as the Mc Multi-Circuit Monitoring Unit for status monitoring and current/voltage measurement across all frame sizes.
Q How does ambient temperature affect the rated current of the SJKM8 circuit breaker?
The rated current of the SJKM8 decreases as ambient temperature rises above the standard 40℃ reference. For example, a 630A breaker rated at 630A at 40℃ will derate to approximately 535A at 70℃. It is important to consult the ambient temperature derating table to ensure correct breaker selection for high-temperature environments.