China Intelligent Wireless Automatic Gas Fire Extinguishing Device - Hot Aerosol Series by China Suppliers & Factory Supplier, Manufacturer

,

Explore our advanced automatic gas fire extinguishing devices, designed for comprehensive protection against electrical fires. Manufactured in China, these intelligent fire suppression systems actively monitor wire temperature, ambient conditions, and smoke levels in real-time. With versatile communication options including RS485, 4G, and Lora, our devices facilitate wireless data uploads to cloud platforms, allowing for seamless remote monitoring and control through computers or mobile apps. As leading suppliers in the industry, our products include the QRR and YF Hot Aerosol series, featuring a modular design for easy cartridge replacement. Trust our factory to provide reliable and cost-effective fire safety solutions tailored for various protected environments.

,

Product Description

Type Designation

QRR MR Type Designation
Model Communication Method Key Features Ideal For
QRR□G/S-MR1 Standalone All-in-one unit with integrated detection & extinguishing. No external communication. Basic protection for small, self-contained spaces.
QRR□G/S-MR2 RS485 Wired Can be integrated into a central fire alarm control panel for centralized monitoring. Buildings or facilities requiring a centralized wired monitoring system.
QRR□G/S-MR3 LORA Wireless Long-range wireless communication. Flexible installation with low network setup cost. Areas with distributed layouts or where wiring is difficult.
QRR□G/S-MR4 4G Wireless Connects directly to the cloud platform. Supports remote monitoring and control via mobile app. Multi-site or cross-regional facilities requiring remote, centralized management.

Product Display

QRR MR Product Showcase Left
QRR MR Product Showcase Right

Product Features

  • ✓ Simultaneous online detection of wire temperature, ambient temperature, and smoke to prevent electrical fire hazards.
  • ✓ Equipped with various communication interfaces such as RS485, 4G, and LoRa.
  • ✓ Wireless data upload to the cloud platform enables viewing of on-site data and remote control via computer or mobile app from any location.
  • ✓ Functions include real-time data collection, historical curves, event recording, and trend analysis.
  • ✓ Two-segment modular product design allows easy replacement of the extinguishing cartridge after use, enabling repeated use and reducing operational costs.

Technical Parameters

Function Configuration QRR □ G/S-MR1 QRR □ G/S-MR2 QRR □ G/S-MR3 QRR □ G/S-MR4
Communication Method / RS485 LORA / 433MHz 4G
Dimensions 0.1G/S: 66×45×90mm
0.3G/S: 66×45×255mm
0.1G/S: 66×45×170mm
0.3G/S: 66×45×335mm
0.1G/S: 66×45×170mm
0.3G/S: 66×45×335mm
0.1G/S: 66×45×170mm
0.3G/S: 66×45×335mm
Operating Voltage / DC24V
Quantity 0.1G/S: 100g±2g  |  0.3G/S: 300g±2g
Protected Space 0.1G/S: ≤1m³  |  0.3G/S: ≤3m³
Discharge Time ≤14s
Discharge Delay Time ≤0.5s
Nozzle Thermal Clearance Temperature at 400mm from nozzle ≤75℃
Surface Temperature of Enclosure ≤75℃
Extinguishing Density 100g/m³ ~ 130g/m³
Service Life 6 Years
Protected Area Requirements Protected area should be relatively enclosed
Installation Method 3M adhesive, strong magnetic adsorption, screw fixation
Operating Environment -40℃ ~ +85℃  |  <95%RH
Activation Method Temperature-based activation:
(when any point of thermal detection line exceeds 170℃)
Logical activation (temperature exceeds 100℃ and smoke detected simultaneously)
Remote activation (via host or cloud platform)
Manual forced start (emergency button, press and hold for 3 seconds)
Over-temperature activation (when any point of thermal detection line exceeds 170℃)

Frequently Asked Questions

Q1What is the difference between QRR-MR1 and QRR-MR4 models?
The QRR-MR1 is a standalone unit with no external communication, making it ideal for simple, self-contained installations. The QRR-MR4 supports 4G wireless connectivity and integrates with a cloud platform, enabling remote monitoring and control via a mobile app — suitable for multi-site or cross-regional management.
Q2What types of fire hazards can the QRR MR series detect?
The QRR MR series simultaneously monitors wire temperature, ambient temperature, and smoke levels, providing comprehensive detection of electrical fire hazards before they escalate.
Q3How is the QRR MR unit installed?
The unit supports three installation methods: 3M adhesive tape, strong magnetic adsorption, and screw fixation, offering flexible options for a wide range of environments and mounting surfaces.
Q4Can the extinguishing cartridge be replaced after activation?
Yes. The two-segment modular design allows the extinguishing cartridge to be easily replaced after use. This enables the device to be reused, significantly reducing long-term operational costs.
Q5What is the protected space volume for each size?
The 0.1G/S model (100g) protects spaces up to 1m³, while the 0.3G/S model (300g) covers spaces up to 3m³. The protected area should be relatively enclosed for optimal performance.
Q6How long is the service life, and what are the operating environment requirements?
The extinguishing agent has a service life of 6 years. The device operates reliably in temperatures ranging from -40°C to +85°C and in humidity conditions below 95%RH, making it suitable for harsh industrial environments.